Inspection
Inspection Details
Equipment ID
9861
9861
Inspection Date
3/7/2023
3/7/2023
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
James Suedkamp
James Suedkamp
Relief Valve Pressure
NA
NA
Slide
C:20";CW:15"
C:20";CW:15"
Governor Rope Pull
C:280/760;CW:230/550
C:280/760;CW:230/550
Door Closing Force
16
16
External ID
5fd038f3-ed1b-4366-af3e-8148c3469298
5fd038f3-ed1b-4366-af3e-8148c3469298
Location
One Financial Plaza
501 N Broadway, St. Louis, MO
Phone: (314) 588-7171
Email: foxr@stifel.com
501 N Broadway, St. Louis, MO
Phone: (314) 588-7171
Email: foxr@stifel.com
Owner
Attn: Jessie Mallioux
One Financial Plaza/Cushman & Wakefield
501 N Broadway, Ste 150, St. Louis, MO 63102
Phone: (314) 588-7171
Email: Jessie.Mallioux@cushwake.com
One Financial Plaza/Cushman & Wakefield
501 N Broadway, Ste 150, St. Louis, MO 63102
Phone: (314) 588-7171
Email: Jessie.Mallioux@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Did not test fire service | 11/3/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 3/11/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell not working | 10/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 2/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The OTIS MCP and documentation for 2021, 2022 & 2023 are missing. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Adjust governor tail sheave to allow compression of car buffer without tail sheaves striking safety arm under car. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly | 11/25/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operational. Re-inspection required | 11/25/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Yes | No | Fire service testing must be documented monthly | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operational. Re-inspection required |