Inspection
Inspection Details
Equipment ID
10190
10190
Inspection Date
3/20/2023
3/20/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Thomas Waters
Thomas Waters
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
fca0204d-24d7-4b77-97b8-826c1fb008ef
fca0204d-24d7-4b77-97b8-826c1fb008ef
Location
700 Market LLC
700 Market St, St. Louis, MO
Phone: (314) 393-9322
700 Market St, St. Louis, MO
Phone: (314) 393-9322
Owner
Attn: Tim Beadle
The Koman Group
8025 Bonhome Ave, Ste 200, Clayton, MO 63105
Phone: (314) 787-1971
Email: TBeadle@Kdgi.com
The Koman Group
8025 Bonhome Ave, Ste 200, Clayton, MO 63105
Phone: (314) 787-1971
Email: TBeadle@Kdgi.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 2/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications/phone not working reinspection item 30 day maximum | 3/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | building currently changing billing 30 day extension has been granted from date of this report | 4/25/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Restrictor is broken and shall be repaired. | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | ALARM BELL SHALL WORK WITH LOSS OF MAIN 120v POWER | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. No extinguisher present | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | 2 electrical boxes in machine room need to have wiring inside box and covers installed. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet. Almost all are blank. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Hoistway door(s) have missing or loose guides on 1st,2nd, and 5th floors. Repair/replace as needed. |