Inspection
Inspection Details
Equipment ID
21385
21385
Inspection Date
3/23/2023
3/23/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
1400
1400
Slide
Inst.
Inst.
Governor Rope Pull
Na
Na
Door Closing Force
35
35
External ID
0cefdb87-42f1-4fae-b188-5e802a54a1ca
0cefdb87-42f1-4fae-b188-5e802a54a1ca
Location
Shaw Elementary School
5329 COLUMBIA AVE, SAINT LOUIS, MO
5329 COLUMBIA AVE, SAINT LOUIS, MO
Owner
Attn: Rosmon Johnson
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Rosmon.Johnson@slps.org
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Rosmon.Johnson@slps.org
Billing
Attn: Cardinal Elevator
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: lisa@cardinalelevator.com
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: lisa@cardinalelevator.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Remove mold from ceiling in elevator machine room. | 8/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance records shall be kept on-site. | 8/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.12 - Car Buffer | 8.11.3.1.5(d) | No | No | Straighten the buffer support in the pit. | 8/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/7/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.13 | Yes | No | OSV tested, failed. Repair as needed. | 4/30/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Observed black mold on the ceiling in the elevator machine room, abate as needed. | 10/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | Yes | No | Door force exceeds code, adjust as needed. | 4/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone | 10/27/2025 |
| A17.1-2016 : Elevators | 2.37 - Pressure Switch | 8.6.5.14.5 | No | No | Repair inoperative low pressure switch | 10/27/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Testing of the OSV needs completed Failed to complete in 2023 | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Replace drywall ceiling section covered in black mold and reseal ceiling to maintain the machine room fire rating | 10/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Observed black mold on the ceiling in the elevator machine room, abate as needed. | 3/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Replace drywall ceiling section covered in black mold and reseal ceiling to maintain the machine room fire rating | 3/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Auxiliary lowering unit was not tested. Reinspection required. |