Inspection
Inspection Details
Equipment ID
8865
8865
Inspection Date
3/24/2023
3/24/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
12
12
External ID
411221a8-86dc-446f-9307-a0436d3a4168
411221a8-86dc-446f-9307-a0436d3a4168
Location
3M Corporation- Springfield
3211 E CHESTNUT EXPY, SPRINGFIELD, MO
Phone: (417) 869-3501
3211 E CHESTNUT EXPY, SPRINGFIELD, MO
Phone: (417) 869-3501
Owner
Attn: 3M Corporation
3M Corporation
3211 E Chestnut Expy, Springfield, MO 65802
Phone: (417) 210-7456
Email: t-cblomquist@mmm.com
3M Corporation
3211 E Chestnut Expy, Springfield, MO 65802
Phone: (417) 210-7456
Email: t-cblomquist@mmm.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | Rubber boot on freight car gate required to be replaced | 9/3/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 9/3/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up date certificate | 4/20/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Replace lamps in fixture located in machine room | 4/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | re fasten top emergency hatch | 4/20/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | Hostway door pull straps missing | 4/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean rubbish from pit | 4/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Check fireman's recall system | 4/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Second & 3rd floor missing pull straps | 10/10/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating Cert. in Mach. room. 5.100(2) | 4/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Must make Emergency light operable. 8.6.4.15 | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Must make emergency alarm operable. 8.6.4.15 | 6/5/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency light operable 8.6.4.15 | 11/4/2024 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Must make emergency light operable. 8.6.4.15 | 11/4/2024 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating Cert. in Mach. room 5.100(2) | 4/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove dirt and rubbish from pit floor | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | remove dirt and rubbish from pit | 5/22/2026 |