Inspection
Inspection Details
Equipment ID
14147
14147
Inspection Date
3/22/2023
3/22/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
na
na
Slide
25
25
Governor Rope Pull
75/800
75/800
Door Closing Force
na
na
External ID
c0ffe332-b083-42fd-9569-b8c0b51fd823
c0ffe332-b083-42fd-9569-b8c0b51fd823
Location
AT & T- Data Center
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
Owner
Attn: AT&T Certificate Mgmt
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Buffer switch needs to be attached tot the buffer | 6/25/2019 | ||
conversion | conversion | conversion - reinspect | x | Emergency light not working on battery backup | 8/19/2018 | |
conversion | conversion | conversion - reinspect | x | Fire service to be tested at a later date. | 8/19/2018 | |
conversion | conversion | conversion - reinspect | x | Alarm bell needs to be sound when stop switch is turned off | 8/19/2018 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Cab emergency light and alarm bell inoperative. | 6/30/2020 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Car top light inoperative. | |||
MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | x | Fire service indicator light is not working, repair same. Re-inspection required | 3/22/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Replace missing pushbuttons/covers on both car operating panels | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | Reversing edge on north car gate is not working, needs repair. Re-inspection required | 3/22/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing push buttons/cover in both operating panels. | |||
MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | x | In car fire service light does not work. Repair same. Reinspection required within 90 days. | 4/20/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Maintenance Control Program records need to be up to date, including monthly fire service checks. | |||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Buzzer on cartop North Side has exposed wiring. Provide proper conduit/cover to enclose wiring. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Provide signage in car in conspicuous place stating: FREIGHT ELEVATOR NO PASSENGERS, and proper class loading. All signage to be at least 1/2" tall | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency communication does not work. Repair same. reinspection required within 90 days. | 4/20/2023 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes are at minimum diameter and need to be shortened. Replace same within 90 days. | 4/20/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Cartop needs to be cleaned. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of current of state certificate of operation needs to be properly displayed in machine room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Reversing edge on North care gate is not working. Repair same. | 4/20/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing pushbuttons / covers in both panels | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | In car fire service light does not work, needs repaired. Re-inspection required within 90 days | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | Buzzer on car top north side has exposed wiring. Provide proper conduit / cover to enclose wiring. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Provide signage in car in conspicuous place stating "FREIGHT ELEVATOR NO PASSENGERS" and proper class loading. All signage to be at least 1/2" tall | |||
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes are at a minimum diameter and need to be shortened, replace the same within 90 days. Re-inspection required | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Cartop needs to be cleaned | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Reversing edge on north car gate is not working, needs repaired. Re-inspection required |