Inspection
Inspection Details
Equipment ID
9725
9725
Inspection Date
3/30/2023
3/30/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
584406f5-ce72-46b7-a6b6-c0012b5d0adb
584406f5-ce72-46b7-a6b6-c0012b5d0adb
Location
Catholic Campus Ministries
847 S Holland Ave, Springfield, MO
Phone: (417) 865-0802
847 S Holland Ave, Springfield, MO
Phone: (417) 865-0802
Owner
Attn: Catholic Campus Ministries
Catholic Campus Ministries
847 S Holland Ave, Springfield, MO 65806
Phone: (417) 865-0802
Email: creichert@ccm847.org
Catholic Campus Ministries
847 S Holland Ave, Springfield, MO 65806
Phone: (417) 865-0802
Email: creichert@ccm847.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | telephone will not call out at all--suspect line-phone needs to go to 24 hr service | 3/6/2019 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 4/1/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating cert. in machine room. 5.100(2) | 4/1/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Must provide current annual test tag on mach. room fire extinguisher. 2.7 | 4/1/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Must provide and maintain MCP Doc. 8.6.1.2.1 | 4/1/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating Cert. in Mach room. 5.100(2) | 4/1/2023 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must perform Category 5 test/insp. for the overspeed valve on or before next annual insp. 8.6.5.16.5 | 4/1/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make emergency phone operable. 8.6.4.15 | 3/30/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Phone Operable. 8.6.4.15 | 7/17/2024 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Must perform and document Cat 5 test for OSV (overspeed valve). 8.6.5.16.5 | 7/17/2024 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | must provide clear buckets to catch oil instead of drain tubes running back to the tank | 7/1/2025 |