Inspection
Inspection Details
Equipment ID
14324
14324
Inspection Date
4/3/2023
4/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
26
26
External ID
f43e8450-8406-4607-b074-f55a9619ee28
f43e8450-8406-4607-b074-f55a9619ee28
Location
Carnahan Building
1114 Market St, St. Louis, MO
Phone: (314) 622-4426
1114 Market St, St. Louis, MO
Phone: (314) 622-4426
Owner
Attn: Terri Bodi
22nd Judicial Circuit Court
1114 Market St, Rm 308, St. Louis, MO 63101
Phone: (314) 622-4721
Email: Terri.Bodi@courts.mo.gov
22nd Judicial Circuit Court
1114 Market St, Rm 308, St. Louis, MO 63101
Phone: (314) 622-4721
Email: Terri.Bodi@courts.mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | 1) Water and oil shall not be allowed to accumulate on pit floors. Ref: 8.6.4.7.4 | 8/27/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | No | No | 2) Firefighters’ Emergency Operation (Phase I and II) shall be tested. Ref: 8.6.4.19.6 | 8/27/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 3) All tests shall be made in accordance with the applicable ASME code as adopted and amended by the Elevator Safety Board. Testing was not completed for 5-year testing. Ref: 5.090 (3)(A) | 8/27/2020 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | NFPA 10- 6.1.3.8.3 Installation Height 4" from floor | No | No | 4) Fire extinguisher shall be in a hanger as per NFPA 13 | 10/8/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | Yes | 1) Firefighters’ Emergency Operation (Phase I and II) shall be tested. Ref: 8.6.4.19.6 | 8/31/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 2) All tests shall be made in accordance with the applicable ASME code as adopted and amended by the Elevator Safety Board. Testing was not completed for 5-year testing. Ref: 5.090 (3)(A) | 8/31/2020 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.10 | Yes | Yes | 3) With a load in the car in accordance with Table 8.6.4.20.4, the braking system and traction relation shall be tested to show the system can safely stop and hold the car. The car failed to safely stop and hold the car. Ref: 8.6.4.20.10(a)(3) | 8/31/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests need to be performed to complete the 5 year full load inspection: full speed counterweight buffer test, 125% brake test, full load, full speed car buffer test, full load, full speed safeties test. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor is not working, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Anti-rotation cable on car top is fraying and needs to be replaced |