Inspection
Inspection Details
Equipment ID
8781
8781
Inspection Date
3/30/2023
3/30/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
10"
10"
Governor Rope Pull
60/550
60/550
Door Closing Force
21
21
External ID
78b62d69-0c3d-4d19-beec-fb926e8943a2
78b62d69-0c3d-4d19-beec-fb926e8943a2
Location
200 South Hanley Bldg
200 S Hanley Rd, Clayton, MO
Phone: (314) 721-7360
200 S Hanley Rd, Clayton, MO
Phone: (314) 721-7360
Owner
Attn: Hoffman
Scott Properties- Hanley
1065 Executive Parkway Dr, St. Louis, MO 63141
Phone: (000) 000-0000
Email: thoffman@scottproperties.com
Scott Properties- Hanley
1065 Executive Parkway Dr, St. Louis, MO 63141
Phone: (000) 000-0000
Email: thoffman@scottproperties.com
Billing
Attn: Carol Crawford
Scott Properties c/o CBRE
1807 Park 270 Dr, Ste 465, St. Louis, MO 63146
Phone: (314) 899-5030
Email: carol.crawford@cbre.com
Scott Properties c/o CBRE
1807 Park 270 Dr, Ste 465, St. Louis, MO 63146
Phone: (314) 899-5030
Email: carol.crawford@cbre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The hoist ropes need to be shortened. | 9/4/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 4/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 6/15/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The person answering the emergency phone shall be able to identify the location of the elevator. | 6/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 6/15/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency alarm bell shall operate when 110v source is removed. | 6/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car door restrictor shall be operational. | 6/15/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)11 | No | No | Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | 1/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 1/2/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/2/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Counterweight guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor. | 1/2/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Only such electrical wiring, raceways, cables, coaxial wiring, and antennas used directly in connection with the elevator shall be permitted to be installed inside the machine room. Remove coaxial wiring. | 1/2/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication phone does not work. Repair or replace code 2.27.1 | 4/22/2025 |