Inspection
Inspection Details
Equipment ID
8477
8477
Inspection Date
4/3/2023
4/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
21
21
External ID
f52bb23c-a07f-4731-b8b6-f4301756637b
f52bb23c-a07f-4731-b8b6-f4301756637b
Location
Boeing Bldg #100
McDonnell Blvd & Airport Rd, Berkeley, MO
Phone: (314) 234-6485
Email: shelbi.paulson@boeing.com
McDonnell Blvd & Airport Rd, Berkeley, MO
Phone: (314) 234-6485
Email: shelbi.paulson@boeing.com
Owner
Attn: Boeing Co
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 234-6485
Email: Kristen.e.wilson@boeing.com
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 234-6485
Email: Kristen.e.wilson@boeing.com
Billing
Attn: Boeing Co
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 234-6485
Email: stlinvoice@boeing.com
Boeing Co
PO Box 516, St. Louis, MO 63166
Phone: (314) 234-6485
Email: stlinvoice@boeing.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door closing over 30 pounds needs adjusting | 6/27/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car not working | 6/27/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair emergency lights | 7/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Repair car door close button | 7/30/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test phase 2 fire service | 3/25/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell shall be operational. | 4/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light shall be operational. | 4/14/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency power shall be tested. | |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | Yes | No | Upper machine level guardrail is only 32" in height. Shall be standard height(42") with midrail (21") and toe kick. | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | Yes | No | Upper machine level lighting shall not be less than 19fc. | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | -Disconnects shall be labeled with location of feeder breakers and function. | |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | Yes | No | All ledges greater than 4" shall be properly guarded and/or beveled at 70deg. | |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | Yes | No | Walkway at top of hoistway shall have proper Standard Handrail w/toekick or 70deg Bevel installed. |