Inspection
Inspection Details
Equipment ID
22035
22035
Inspection Date
4/5/2023
4/5/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
480
480
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
20
20
External ID
10eec439-f2ac-4a0a-be8b-1437e838fca9
10eec439-f2ac-4a0a-be8b-1437e838fca9
Location
Holiday Inn Express
10000 Natural Bridge Rd, St. Louis, MO
Phone: (314) 280-5330
10000 Natural Bridge Rd, St. Louis, MO
Phone: (314) 280-5330
Owner
Attn: Holiday Inn Express
Holiday Inn Express of St. Louis Airport
10000 Natural Bridge Rd, St. Louis, MO 63134
Phone: (000) 000-0000
Holiday Inn Express of St. Louis Airport
10000 Natural Bridge Rd, St. Louis, MO 63134
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light does not work. | 4/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean pit. | 12/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | Replace cover on hoistway door lock assembly. | 12/21/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operable | 7/5/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator has a rupture valve that has been sealed but not tagged, this test shall be performed between now and the end of the year. | 12/21/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room a/c is leaking water and the water is dripping on an electrical junction box and shall be repaired | 12/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 12/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work correctly. | 12/4/2024 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV in the pit is due for testing, provide. | 12/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | Cylinder(s) packing is worn and leaking repair as needed. | 12/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 12/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit. | 12/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is due for testing, provide. | 12/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 12/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | Packing is worn and leaking, repair or replace as needed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | Packing is worn and leaking, repair or replace as needed. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Elevator machine room shall be cleaned and clear of obstructions | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing | |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Overspeed valve is sealed but has not been tested. Overspeed valve needed to be tested in 2023. Inspect within 30 days |