Inspection
Inspection Details
Equipment ID
21724
21724
Inspection Date
4/12/2023
4/12/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Na
Na
Slide
9”
9”
Governor Rope Pull
50/400
50/400
Door Closing Force
19
19
External ID
5a1ffbf8-9a0d-4588-9d47-cdc96e7d496c
5a1ffbf8-9a0d-4588-9d47-cdc96e7d496c
Location
River City Casino Hotel
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO
Phone: (314) 915-7836
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO
Phone: (314) 915-7836
Owner
Attn: River City Hotel
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@pngaming.com
PNK (River City) LLC
777 River City Casino Blvd, St. Louis, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@pngaming.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not call out. | 6/15/2022 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | x | Coated steel belt monitor fault code says to replace belts immediatly. Replace coated steel belts. Red-tagged, Re-inspection required | 9/14/2022 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work, line problem. Re-inspection required | 9/14/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required in 14 days. | 4/3/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | The lighting in the machine space overhead failed to operate on the day of testing. The lighting shall be repaired for maintenance and emergency personnel. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Elevator appears to have emergency generator backup power operation, which needs to be tested to complete inspection. Re-inspection required | 5/22/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working correctly. Check and repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 5/22/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | The lighting in the machine space overhead failed to operate on the day of testing. The lighting shall be repaired for maintenance and emergency personnel | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly, check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 5/21/2024 | |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | The lighting in the machine space overhead failed to operate on the day of testing, needs to be repaired | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly. Check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 10/1/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | The lighting in the machine space overhead failed to operate on the day of testing. The lighting shall be repaired for maintenance & emergency personnel. |