Inspection
Inspection Details
Equipment ID
10423
10423
Inspection Date
4/11/2023
4/11/2023
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Conde (Cache) Kinsella
Conde (Cache) Kinsella
Mechanic Name
Francis Klocke
Francis Klocke
Relief Valve Pressure
N/A
N/A
Slide
23
23
Governor Rope Pull
60/470
60/470
Door Closing Force
15
15
External ID
2a36efa8-f4ec-47bd-a8cf-571b91b9d86e
2a36efa8-f4ec-47bd-a8cf-571b91b9d86e
Location
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
Owner
Attn: Jason DeLashmit
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: jason.delashmit@mercy.net
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: jason.delashmit@mercy.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit shall be cleaned of dust and debris. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency light fixture inside the elevator is not operational and shall be repaired. | 7/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Re-inspection is required. | 7/18/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted. The Audible signal device did not sound when phase I was activated. | 7/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency car lighting is not operational. The fixture shall be repaired to operate. | 8/13/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II operation, the elevator car will not override the security feature on the car operating panel. Security shall be overridden in fireman’s service. | 8/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II operation, the elevator car will not override the security feature on the car operating panel. Security shall be overridden in fireman’s service. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 8/10/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Replace the deteriorating guide roller on top of the elevator car. | 11/22/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel. | 11/22/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 8/16/2022 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | No | No | The electrical ductwork at the top of the hoistway is missing the top portions cover. Install a duct cover. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | emergency two way communication device is inoperable | 8/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator and fire service testing shall be done. Scheduled 8/19/25 | 8/19/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication device is inoperable. Re-inspection required |