Inspection
Inspection Details
Equipment ID
17351
17351
Inspection Date
10/3/2018
10/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Arthur Roach
Arthur Roach
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
16
16
External ID
0f48189d-d738-4c07-ba56-b240531dc2c6
0f48189d-d738-4c07-ba56-b240531dc2c6
Location
St. Luke's Hospital
100 NE SAINT LUKES BLVD, LEES SUMMIT, MO
100 NE SAINT LUKES BLVD, LEES SUMMIT, MO
Owner
St. Luke's Hospital
100 NE SAINT LUKES BLVD, LEES SUMMIT, MO 64086-6000
100 NE SAINT LUKES BLVD, LEES SUMMIT, MO 64086-6000
Billing
Attn: St. Luke's Hospital
100 NE SAINT LUKES BLVD, LEES SUMMIT, MO 64086-6000
100 NE SAINT LUKES BLVD, LEES SUMMIT, MO 64086-6000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | x | cables need to be shortened less than 6 ins between CW an spring | 1/24/2022 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emg lt. an bell not working | 1/24/2022 | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.11.2.1.1(r) | x | door restrictor not working | 1/24/2022 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | emg. power couldnt be tested at time of insp | 1/24/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | x | emg power lt not working | 11/17/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.3.5 | x | Emergency power not tested at time of inspecion. | 1/10/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 2.15.9 | toe guards are less than 48ins. | 9/10/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt displayed | 9/10/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Emg power couldnt be done at time of insp. | 4/15/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | x | runby less than 6'' between spring buffer an counterweight shorten ropes | 4/15/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 2.15.9 | need 48in toe guard unit has rope gripper | 9/10/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | emg power jewel not lighting | 10/27/2025 |