Inspection
Inspection Details
Equipment ID
12988
12988
Inspection Date
4/14/2023
4/14/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
a
a
Slide
na
na
Governor Rope Pull
50/500
50/500
Door Closing Force
25
25
External ID
49d6f646-5a21-483f-898f-5f06f2f48d2d
49d6f646-5a21-483f-898f-5f06f2f48d2d
Location
Chase Park Plaza Hotel
212 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
212 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 633-1000
Owner
Attn: Paul Smith
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1009
Alt Phone: (314) 363-4990
Email: psmith@sonesta.com
Billing
Attn: Accounts Payable
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: SonestaAP@yardifs.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: SonestaAP@yardifs.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install tack wiring in conduit or duct in machine room | 3/31/2026 |
| conversion | conversion | n/a | No | No | Pit should be clean and drive remove water and debris | 3/31/2026 |
| conversion | conversion | conversion - reinspect | Yes | No | 18 repair door restrictor | 4/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency lights do not work. | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not work on battery back-up power. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | No | No | Suspension ropes are rouged and undersized and need to be replaced. REINSPECT WITHIN 30 DAYS | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 8.6.4.11 | Yes | No | Clean elevator car top. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone - does not work with power off. | 4/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Need to shorten ropes. Re-inspection required | 4/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Elevator machine room air conditioner is not working. 90 degrees F at time of inspection. Repair | 3/31/2026 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.19.16 | Yes | No | Door restrictor inoperable (damaged), repair car door restrictor | 4/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Full load test incomplete. Test car buffer with rated load at rated speed. Test car safeties with rated load at rated speed. Test driving machine brake with 125% of rated load. | 4/3/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 5/20/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. |