Inspection
Inspection Details
Equipment ID
25625
25625
Inspection Date
4/20/2023
4/20/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Ronald Gist
Ronald Gist
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
9f086206-9ee3-4bdd-9291-5e18d47d97ed
9f086206-9ee3-4bdd-9291-5e18d47d97ed
Location
Parkdale Manor Care Center
814 W S Ave, Maryville, MO
Phone: (660) 582-8161
814 W S Ave, Maryville, MO
Phone: (660) 582-8161
Owner
Attn: Matt Libbert
Parkdale Manor Care Center
814 W S Ave, Maryville, MO 64468
Phone: (573) 230-9287
Email: mlibbert@jmsseniorliving.com
Parkdale Manor Care Center
814 W S Ave, Maryville, MO 64468
Phone: (573) 230-9287
Email: mlibbert@jmsseniorliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | Machine access door must be self closing/self locking | 3/15/2022 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine space access door needs to be self-closing and self-locking. | 4/20/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan on site. | 4/20/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | No wiring diagrams on site. | 4/20/2023 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Post code data plate on controller or disconnect. "ASME A17.1 2016" | 4/20/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(d) | No | No | No permanent test tag of acceptance inspection on controller or on site. | 4/20/2023 |
| A17.1-2016 : Elevators | 4.4 - Hoistway door locking devices | 8.11.2.1.4(d) | Yes | Yes | Need to test integrity of door lock and contact on lower landing hoistway door. Could not test integrity because the dumbwaiter was not operating. Door and door lock assembly was installed after initial inspection. | 7/21/2022 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | Yes | Yes | Distance between face of swing landing door and edge of hoistway sill exceeds 3 inches. A17.1 7.1.11.4.2 | 4/20/2023 |
| A17.1-2016 : Elevators | 1.7 - Car door or gate | 2.14.4 | Yes | Yes | Horizontally sliding collapsible car gate shall have every fourth vertical member guided at the top and every second vertical member guided at the bottom. There are no guides on the bottom and the gate can swing out from the car in the fully open (collapsed) position. A17.1 7.2.1.2.4(4) | 4/20/2023 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Post code data plate on controller or disconnect. | 4/20/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(d) | No | No | No permanent test tag on controller. | 4/20/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | No maintenance control plan on site | 4/20/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance record log on site | 4/20/2023 |