Inspection
Inspection Details
Equipment ID
18665
18665
Inspection Date
4/10/2023
4/10/2023
Inspection Type
Alteration
Alteration
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
135/620
135/620
Door Closing Force
na
na
External ID
4197a580-1527-4158-812e-3eb2ee432bfa
4197a580-1527-4158-812e-3eb2ee432bfa
Location
AmeriStar Casino
1 Ameristar Blvd, St. Charles, MO
Phone: (636) 940-4340
Alt Phone: (314) 809-9134
Email: Patmcdonald@boydgaming.com
1 Ameristar Blvd, St. Charles, MO
Phone: (636) 940-4340
Alt Phone: (314) 809-9134
Email: Patmcdonald@boydgaming.com
Owner
Attn: AmeriStar Casino- St. Charles LLC
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
Billing
Attn: AmeriStar Casino- St. Charles, LLC
AmeriStar Casino- St. Charles LLC
1 Ameristar Blvd, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
AmeriStar Casino- St. Charles LLC
1 Ameristar Blvd, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that per the manufacturer specifications it shall be “replaced within 6 months”. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. | 2/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 7/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | Yes | No | Upon performing the required five year full load, the elevator controller failed to allow the elevator to perform the 125% of rated load lowering test. This appears to be a “load weighing” or “controller” issue as the physical operation of the mechanical brake does lower and hold 125% of the rated load. The controller/load weighing shall be repaired and a reinspection with 125% performed before the inspection is completed. | 2/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that per the manufacturer specifications it shall be “replaced within 2 months”. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. | 4/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller | 8/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | Yes | No | Upon performing the required five year full load, the elevator controller failed to allow the elevator to perform the 125% of rated load lowering test. This appears to be a “load weighing” or “controller” issue as the physical operation of the mechanical brake does lower and hold 125% of the rated load. The controller/load weighing shall be repaired and a reinspection with 125% performed before the inspection is completed. | 4/10/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly. | 4/10/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 4/10/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 4/10/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required. | 8/9/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | There are a number of machine room lighting fixtures that are not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 8/9/2023 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller | 8/9/2023 |
| A17.1-1996 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 102.1 | Yes | No | The controller/load weighing shall be repaired and a reinspection with 125% performed before the inspection is completed. | 1/19/2024 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | The elevator hoisting belts are showing a high degree of wear and shall be replaced. Replace belts within 30 days of inspection. Reinspection is required. | 5/29/2026 |