Inspection
Inspection Details
Equipment ID
18665
18665
Inspection Date
4/10/2023
4/10/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
98b69e62-2594-4489-b597-76c39f846281
98b69e62-2594-4489-b597-76c39f846281
Location
AmeriStar Casino
1 Ameristar Blvd, St. Charles, MO
Phone: (636) 940-4340
Alt Phone: (314) 809-9134
Email: Patmcdonald@boydgaming.com
1 Ameristar Blvd, St. Charles, MO
Phone: (636) 940-4340
Alt Phone: (314) 809-9134
Email: Patmcdonald@boydgaming.com
Owner
Attn: AmeriStar Casino- St. Charles LLC
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
Phone: (000) 000-0000
Billing
Attn: AmeriStar Casino- St. Charles, LLC
AmeriStar Casino- St. Charles LLC
1 Ameristar Blvd, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
AmeriStar Casino- St. Charles LLC
1 Ameristar Blvd, St. Charles, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that per the manufacturer specifications it shall be “replaced within 6 months”. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. | 2/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 7/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | Yes | No | Upon performing the required five year full load, the elevator controller failed to allow the elevator to perform the 125% of rated load lowering test. This appears to be a “load weighing” or “controller” issue as the physical operation of the mechanical brake does lower and hold 125% of the rated load. The controller/load weighing shall be repaired and a reinspection with 125% performed before the inspection is completed. | 2/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that per the manufacturer specifications it shall be “replaced within 2 months”. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. | 4/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller | 8/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.6.3 | Yes | No | Upon performing the required five year full load, the elevator controller failed to allow the elevator to perform the 125% of rated load lowering test. This appears to be a “load weighing” or “controller” issue as the physical operation of the mechanical brake does lower and hold 125% of the rated load. The controller/load weighing shall be repaired and a reinspection with 125% performed before the inspection is completed. | 4/10/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly. | 4/10/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 4/10/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 4/10/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required. | 8/9/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | There are a number of machine room lighting fixtures that are not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 8/9/2023 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller | 8/9/2023 |
| A17.1-1996 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 102.1 | Yes | No | The controller/load weighing shall be repaired and a reinspection with 125% performed before the inspection is completed. | 1/19/2024 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | The elevator hoisting belts are showing a high degree of wear and shall be replaced. Replace belts within 30 days of inspection. Reinspection is required. | 5/29/2026 |