Inspection
Inspection Details
Equipment ID
17416
17416
Inspection Date
4/26/2023
4/26/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
26
26
External ID
65b81482-3028-4c4e-875b-3abee567c95c
65b81482-3028-4c4e-875b-3abee567c95c
Location
South Side Towers
3611 GRAVOIS AVE, SAINT LOUIS, MO
Phone: (314) 776-7000
3611 GRAVOIS AVE, SAINT LOUIS, MO
Phone: (314) 776-7000
Owner
Attn: Adam Belsky
South Side Tower c/o Rodemyer Christel, Inc
3630 Grandel Sq, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 302
Email: abelsky@rcirealty.com
South Side Tower c/o Rodemyer Christel, Inc
3630 Grandel Sq, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 302
Email: abelsky@rcirealty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 5/13/2019 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(t) | Yes | No | Repair brakes failed 125% red tagged unit reinspection required | 4/8/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove non elevator storage from machine room | 3/24/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 3/24/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 3/24/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/24/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 3/24/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications/phone in car not working reinspection item 30 day maximum | 9/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Generator/standby power needs to be tested reinspection item maximum 30 days to complete | 9/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Emergency power indicator inoperative | 4/21/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator is equipped with emergency power. The operation of elevators equipped with standby or emergency power shall be tested annually to determine conformance with the applicable requirements. The generator technician said he was unable to perform the test, and needs to order replacement parts. | 3/24/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Could not get generator started | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Emergency communications/phone in car not working. |