Inspection
Inspection Details
Equipment ID
9611
9611
Inspection Date
4/21/2023
4/21/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Jeff Stanley
Jeff Stanley
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
d15c1264-a742-4d2e-9208-78071a2394e2
d15c1264-a742-4d2e-9208-78071a2394e2
Location
Kauffman Stadium
103 ROYAL WAY, KANSAS CITY, MO
Phone: (816) 921-9000
103 ROYAL WAY, KANSAS CITY, MO
Phone: (816) 921-9000
Owner
Attn: Kauffman Stadium
Kauffman Stadium
1 Royal Way, Kansas City, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Kauffman Stadium
1 Royal Way, Kansas City, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | replace the battery on the emergency phone, it would not dial out with the 110 volt power is off | 7/8/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current copy of the State Operating Certificate in the machine room | 5/13/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Post monthly fire service test log in the machine room | 5/13/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Post instructions for viewing on-site the records for the Maintenance Control Program (MCP) | 5/13/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 5/13/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 5/13/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | the state operating certificate in the machine room is from 2013, it is to be updated every year with a new copy | 5/13/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | a monthly fire service test log is to be kept in the machine room | 5/13/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | have Maintenance Control Program (MCP) book in the machine room | 5/13/2025 | ||
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | x | OSV NOT TESTED AT THIS TIME TO VERIFY OPERATION | 3/12/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Supply working phone (no input to controller) | 3/13/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Only elevator related material allow in machine room | 3/12/2025 |