Inspection
Inspection Details
Equipment ID
4655
4655
Inspection Date
4/26/2023
4/26/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Nicolas Dominguez
Nicolas Dominguez
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
40330a83-f736-4f7a-aab9-ef95371e1ebb
40330a83-f736-4f7a-aab9-ef95371e1ebb
Location
Kauffman Stadium
103 ROYAL WAY, KANSAS CITY, MO
Phone: (816) 921-9000
103 ROYAL WAY, KANSAS CITY, MO
Phone: (816) 921-9000
Owner
Attn: Kauffman Stadium
Kauffman Stadium
1 Royal Way, Kansas City, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Kauffman Stadium
1 Royal Way, Kansas City, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Handrail is cracked, fissure on side of handrail | 7/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.5 | No | No | submit results of the skirt index performance test | 7/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.7 - Combplate and comb step impact device | 8.10.4.1.1(g) | No | No | replace broken comb plates at the top and bottom | 7/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Submit results of skirt index test | 3/19/2021 |
| A17.1-2016 : Elevators | 7.9 - Steps and upthrust device | 8.11.4.1(i) | No | No | The steps shall be kept clean and free of debris such as bird droppings | 7/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 8.11.4.1 (c) | No | No | Handrails shall be kept clean of bird droppings as this is where passengers hold onto for safety | 7/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 8.11.4.1 (c) | No | No | repair / replace left handrail, it is ripped in more than one place that can be pinch hazards | 7/1/2025 |
| A17.1-2016 : Elevators | 7.9 - Steps and upthrust device | 8.11.4.1(i) | No | No | The steps shall be kept clean and free of debris, such as bird droppings. | 7/1/2025 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.11.4.1(c) | No | No | The handrails shall be kept clean of bird droppings, as this is where the passengers hold onto for safety. | 7/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | submit results of skirt index test | 4/26/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.13 - Handrail systems and safety devices | 8.11.4.2.13 | No | No | Replace damaged handrail pieces missing from side of rail | 5/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.9 - Steps and upthrust device | 6.1.6.3.9 | Yes | No | UPPER UP THRUST SWITCH REACTS OVER 150 | 10/30/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | PROVIDE REQUIRE SKIRT INDEX TEST | 10/30/2024 |