Inspection
Inspection Details
Equipment ID
26102
26102
Inspection Date
5/1/2023
5/1/2023
Inspection Type
Temporary Certificate Inspection
Temporary Certificate Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Justin Scherrer
Justin Scherrer
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
65c2d1ad-8a11-4066-96f7-751add90608b
65c2d1ad-8a11-4066-96f7-751add90608b
Location
Streets of St. Charles
333 Mulholland Dr, St. Charles, MO
Phone: (000) 000-0000
333 Mulholland Dr, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: Chapter at the Streets, LLC
Chapter at the Streets, LLC
333 Mulholland Dr, St. Charles, MO 63303
Phone: (000) 000-0000
Email: chart@brinkmannconstructors.com
Chapter at the Streets, LLC
333 Mulholland Dr, St. Charles, MO 63303
Phone: (000) 000-0000
Email: chart@brinkmannconstructors.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase machine space illumination to 19 ft-candles minimum | 5/11/2023 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase machine space lighting to 19 ft-candles minimum | 5/11/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | Provide shunt trip for mainline. Activated by a heat detector | 5/11/2023 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | Yes | No | Provide a means of smoke control in the hoistway compliant with the building code | 5/11/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. | 8/27/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted convient to the machine room door. | 12/3/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.7.6.3.4 | Yes | No | The remote governor tripping/reset means on the controller (means to test) shall be operational. | 8/27/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.7.6.3.4 | Yes | No | The remote governor tripping/reset means on the controller (means to test) shall be operational. | 11/25/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The emergency power jewel at main lobby does not illuminate when emergency power operation is enabled. | 12/3/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually. | 5/22/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | Compliant/required documentation shall be kept on-site including MCP wiring diagrams, PM log, callback log, and evacuation procedures. No such documentation on-site for 2023, 2024, and 2025. | 4/7/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/7/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No State operating certificate in the machine room. | 5/6/2026 |