Inspection
Inspection Details
Equipment ID
1656
1656
Inspection Date
4/26/2023
4/26/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Na
Na
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26
26
External ID
a41b2974-dea7-41f5-91ca-da0c428a257d
a41b2974-dea7-41f5-91ca-da0c428a257d
Location
10 South Broadway Bldg
10 S Broadway, St. Louis, MO
Phone: (314) 421-3480
10 S Broadway, St. Louis, MO
Phone: (314) 421-3480
Owner
Attn: Hertz Investment Group
Hertz Investment Group
10 S Broadway, Ste 100, St. Louis, MO 63102
Phone: (314) 421-3480
Email: KEbling@hertzgroup.com
Hertz Investment Group
10 S Broadway, Ste 100, St. Louis, MO 63102
Phone: (314) 421-3480
Email: KEbling@hertzgroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency light shall work. | 9/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fireman's recall was not tested. | 4/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 8.11.2.2.5 | Yes | No | Needs to be tested. | 8/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | ETS needs to be tested. | 9/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Fire service maintenance records need to be placed in machine room. | 9/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(1) Wire ropes shall be replaced | Yes | Yes | Ropes are undersized. Car must be reroped and reinspected within 30 days. Did not red tag. | 8/9/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone | 5/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Provide existing lights and bell . | 7/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone works, when 110v disconnected, phone needs to work on battery backup. | 7/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 7/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | No | No | Provide testing of the elevator emergency power selector switch. | 9/3/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 9/3/2025 |