Inspection
Inspection Details
Equipment ID
18912
18912
Inspection Date
5/2/2023
5/2/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Glen Fehrenbacher
Glen Fehrenbacher
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
54960ecf-3570-414d-8e0e-a4b9ba85ea02
54960ecf-3570-414d-8e0e-a4b9ba85ea02
Location
Horseshoe Casino
999 N 2nd St, St. Louis, MO
Phone: (314) 881-7782
999 N 2nd St, St. Louis, MO
Phone: (314) 881-7782
Owner
Attn: Frank Prusinowski
Four Seasons Hotel
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-2072
Email: frank.prusinowski@fourseasons.com
Four Seasons Hotel
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-2072
Email: frank.prusinowski@fourseasons.com
Billing
Attn: Erika Icenhower
Four Seasons Hotel
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-2072
Email: EIcenhower@lumiereplace.com
Four Seasons Hotel
999 N 2nd St, St. Louis, MO 63102
Phone: (314) 881-2072
Email: EIcenhower@lumiereplace.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair malfunctioning upper demarcation lights. | 12/8/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Both handrails have cracks. Replace | 12/8/2025 |
| A17.1-1996 : Escalators | 8.4 - Drive machine and brake | 804 | Yes | Yes | Brake torque failed. Shut unit off. | 11/22/2019 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Demarcation lights on both ends are out. | 12/8/2025 |
| A17.1-1996 : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Certificate | No | No | Display updated operating certificate in machine room. | 12/8/2025 |
| A17.1-1996 : Escalators | 7.9 - Steps and upthrust device | 802.6e | No | No | Step demarcation strips - 3 are broken | 12/8/2025 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 802.6 | No | No | Replace lower comb section. broken tooth. | 12/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 8.11.4.2.13 | No | No | Right handrail is cracked. Must be replaced. | 12/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 8.6.11.5(i) Demarcation Lighting (Re-Inspect) | Yes | No | Demarcation strip on step is broken. | 4/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.7 - Combplate and comb step impact device | 6.1.6.3.13 | Yes | Yes | Vertical comb step impact device does not actuate until 300 lbs. the maximum allowed is 150 lbs for vertical Impact | 5/2/2023 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.9 - Steps and upthrust device | 6.1.3.5 | Yes | No | Replace damaged demarcation strips as needed. Re-inspection required | 4/28/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair top demarcation light. Re-inspection required | 4/28/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Both handrails have cracks, need to be replaced. | 12/8/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.6.2(i) Step Demarcation | No | No | Need to replace damaged demarcation strips as needed | 12/8/2025 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.13 - Handrail systems and safety devices | 6.1.3.4 | No | No | Left Handrail shall be adjusted to not stall during normal operation |