Inspection
Inspection Details
Equipment ID
8278
8278
Inspection Date
3/20/2023
3/20/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
NA
NA
Slide
TBD
TBD
Governor Rope Pull
140/500
140/500
Door Closing Force
27
27
External ID
91c03deb-7159-4ddf-bdbc-ce873329eac1
91c03deb-7159-4ddf-bdbc-ce873329eac1
Location
St. Louis Police Department
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
Owner
Attn: David Cleveland
St. Louis City of- Police Dept
1200 Clark Ave, St. Louis, MO 63103
Phone: (314) 622-4635
Email: clevelandd@stlouis-mo.gov
St. Louis City of- Police Dept
1200 Clark Ave, St. Louis, MO 63103
Phone: (314) 622-4635
Email: clevelandd@stlouis-mo.gov
Billing
Attn: Rick Ernst
St. Louis City of- Police Dept
1200 Clark Ave, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
St. Louis City of- Police Dept
1200 Clark Ave, St. Louis, MO 63103
Phone: (314) 622-4635
Email: ernstr@stlouis-mo.gov
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | All lighting in the machine room shall be operational. | 5/21/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested ABC type fire extinguisher shall be provided in the elevator machine room. Current extinguisher is expired. | 5/21/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The controller air conditioning shall be operational. | 4/13/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational on auxiliary power. | 5/13/2022 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | 8.11.2.1.1(y) - Seismic "earthquake direction switch" shall be operational. | 5/13/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The wiring in the pit shall be enclosed. (Note: A box cover is missing) | 4/13/2026 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | No | No | The elevator machine room shall be protected from the weather. (Note: Windows are being left open, and the equipment and machine room floor are showing signs that they have been wet, possibly from a leaky roof). | 4/13/2026 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height. (Note: The COP should be identified as car 1 as it is in the machine room). | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 102.4 | No | No | The controller air conditioning shall be operational. | 4/13/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP Fire Service testing must be properly documented monthly on log sheet. There is no log present. | 4/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete due to elevator operational failure. Needs: all tests that include weight, buffers, pit, fire service 1 & 2, runby. | 9/1/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with loss of main 120v power. | 3/14/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency lighting shall work. | 3/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Suspension rope tail ends shall be properly seized/banded and retaining clips shall be set at proper distance. | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/13/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work. | 9/11/2024 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. | 9/11/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Cab lighting - All lamps shall work, none working. | 4/13/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have current tested and tagged fire extinguisher. No extinguisher in room or immediately adjacent to door. | 4/13/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating permit shall be obtained and displayed in the equipment room. | 4/13/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 4/13/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. This violation must be corrected immediately per the AHJ. | 3/4/2025 |