Inspection
Inspection Details
Equipment ID
10456
10456
Inspection Date
10/4/2018
10/4/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Matthew Hilling
Matthew Hilling
Relief Valve Pressure
310
310
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
00a7f883-c04c-4c23-bd27-047ce2826cb6
00a7f883-c04c-4c23-bd27-047ce2826cb6
Location
Washington Medical Arts
4585 WASHINGTON ST, FLORISSANT, MO
4585 WASHINGTON ST, FLORISSANT, MO
Owner
Washington Medical Arts
100 COUNTRY BROOK CT, SAINT CHARLES, MO 63303-6431
100 COUNTRY BROOK CT, SAINT CHARLES, MO 63303-6431
Billing
Attn: Washington Medical Arts
3409 WOOLEN MILL ST, SAINT CHARLES, MO 63301-8168
3409 WOOLEN MILL ST, SAINT CHARLES, MO 63301-8168
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. | 10/17/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 10/17/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. A telephone cabinet has been dislodged from the wall that is impeding the area for proper maintenance to be performed. | 10/17/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Repair machine room door closer. Door to be self-closing and locking. | 12/31/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Increase machine room lighting to 10 ft candles throughout, measured at the floor. | 12/31/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide a written maintenance control program | 11/8/2021 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | The distance between the face of the controller and the nearest obstruction shall be no less than 36". | 1/21/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication line does not work. | 1/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | There is a sprinkler at the top of hoistway, but no heat or smoke detector. | 1/21/2025 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Yes | No | Cab lights need to be repaired or replaced to provide code compliant lighting. | 1/21/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The phone inside the car does not work. | 1/21/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | The distance between the face of the controller and the nearest obstruction shall be no less than 36". Note: Customer may be applying for a variance. |