Inspection
Inspection Details
Equipment ID
25249
25249
Inspection Date
4/11/2023
4/11/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Anthony Wunderlich
Anthony Wunderlich
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
575834c8-a2a9-4af9-b8bc-c3dcc14b7c08
575834c8-a2a9-4af9-b8bc-c3dcc14b7c08
Location
TCI Products Inc.
2216 N Broadway, St. Louis, MO
Phone: (314) 560-9904
2216 N Broadway, St. Louis, MO
Phone: (314) 560-9904
Owner
Attn: TCI Products Inc.
TCI Products Inc.
2216 N Broadway, St. Louis, MO 63102
Phone: (314) 231-3075 Ext: 305
Alt Phone: (314) 560-9904
Email: Mike.Hase@TCIProducts.com
TCI Products Inc.
2216 N Broadway, St. Louis, MO 63102
Phone: (314) 231-3075 Ext: 305
Alt Phone: (314) 560-9904
Email: Mike.Hase@TCIProducts.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The elevator enclosure shall be extended to the top of the cab. The area that passes the counterweight shall be solid material. | 8/11/2022 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)4 | No | No | The car top shall be completely covered and be able to support a 200 lbs. weight. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The car stop switch shall be operational. | 8/11/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace the missing interlock covers where needed. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking. | |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | The lower limit switches shall be raised up to the first floor if the lower landing is no longer in use. | 8/11/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Provide a permanent pit stop switch adjacent to the pit door. | 8/11/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | A permanent light fixture shall be installed in the pit with the switch adjacent to the bottom floor door. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Replace all broken slats on front & rear gates. | 8/11/2022 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | A permanent capacity plate and a "No Passengers" sign shall be installed. | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a permanent, non-combustible pit sump pump cover. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide a code compliant MCP including onsite documents. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work. | 4/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Second floor limit switch (floor selector switch) is not working in the UP direction. | 4/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | The SOS is not operating. Elevator Red Tagged. | 4/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work. | 6/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Second floor limit switch (floor selector switch) is not working in the UP direction. | 6/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Unit red tagged due to car being able to run with car gate and/or hoistway doors open. | 4/11/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | Yes | No | Install emergency stop switch in pit. | 4/11/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | All means of access to elevator machine rooms shall be constructed and maintained in a clear and unobstructed manner. Need permanent stairs into machine room. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Entirety of the annual testing shall be completed. Testing stopped due to red tag. | 4/11/2025 |