Inspection
Inspection Details
Equipment ID
23909
23909
Inspection Date
4/18/2023
4/18/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
9518eaee-0eff-4be1-9f78-6a3a1e30158f
9518eaee-0eff-4be1-9f78-6a3a1e30158f
Location
Comfort Inn Mainstay Suites
11225 Lone Eagle Dr, Bridgeton, MO
Phone: (000) 000-0000
11225 Lone Eagle Dr, Bridgeton, MO
Phone: (000) 000-0000
Owner
Attn: Rocky Patel
AK Hospitality LLC
11225 Lone Eagle Dr, Bridgeton, MO 63044
Phone: (916) 799-9246
Email: Stlmaincomfort@gmail.com
AK Hospitality LLC
11225 Lone Eagle Dr, Bridgeton, MO 63044
Phone: (916) 799-9246
Email: Stlmaincomfort@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide an elevator maintenance log. | 10/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A monthly fire service testing log shall be kept on-site. | 10/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Verify the function on the heat detector at the top of the hoistway and if it has any effect on the operation of the elevator. | 3/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Clean the elevator pit of dirt and debris. | 10/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 5/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures, maintenance/repair records, and monthly fire service checklist are missing. | 5/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve, along with an installation date of 2017. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 5/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The following violation was cited during the 2019 annual inspection and has not been verified. The following item shall be re-inspected: Verify the function on the heat detector at the top of the hoistway and if it has any effect on the operation of the elevator. | 4/18/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 9/29/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | The overspeed valve has an installation date of 2017. The overspeed valve is due for a category 5 test. | 9/29/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. Phone is not working on battery backup. | 3/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering unit is not working. | 3/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device is not functioning when power is removed from unit. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Auxiliary power lowering operation is not functional. |