|
conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
In cab emergency telephone shall work.
|
8/9/2018
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
6/11/2021
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
6/11/2021
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
6/11/2021
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car emergency telephone shall be operational.
|
6/11/2021
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
No
|
No
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
6/11/2021
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures, repair and maintenance logs, and testing procedures are missing.
|
8/8/2022
|
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(5) Oil Leakage Collection
|
No
|
No
|
A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. Note: Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas.” Note: The oil recovery system on this unit is gravity fed, which isn't allowed.
|
8/17/2023
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency two-way communication device is not functional and needs repaired.
|
|