Inspection
Inspection Details
Equipment ID
4851
Inspection Date
2/14/2023
Inspection Type
Annual Inspection
Inspector Name
Daniel Letcher
Mechanic Name
Jeff Stanley
Relief Valve Pressure
n/a
Slide
not completed
Governor Rope Pull
not completed
Door Closing Force
not completed
External ID
3575db6b-bfd7-4935-9afb-f7dfb0b3f334
Location
Temple Heights Manor I
5420 Blue Ridge Cut Off, Raytown, MO
Phone: (816) 358-9537
Owner
Attn: Temple Heights
Temple Heights Manor dba Temple Heights Manor I
5420 Blue Ridge Cut Off, Raytown, MO 64133
Phone: (660) 864-0529
Email: manager@templeheightsmanor.com
Violations
|
Code
|
Item
|
Section
|
Reinspection
|
Red Tag
|
Reason For Violation
|
Fixed Date
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
Yes
|
No
|
The host ropes need to have the tension equalized, one of the ropes has almost no tension on it compaired to the others.
|
3/29/2019
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
No
|
No
|
A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
|
6/18/2021
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.10.2
|
No
|
No
|
the elevator lobby lights at each landing were not working at the time of the inspection.
|
6/18/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
phone dials and then hangs up before operator can answer the phone, repair and retest
|
4/5/2022
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
the state operating certificate in the machine room is to be updated with a new copy every year
|
4/5/2022
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
No
|
No
|
there is to be a monthly fire service test log posted in the machine room
|
4/5/2022
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
No
|
No
|
machine room air conditioning unit does not appear to be keeping the room cool, verify proper operation of the air conditioner to keep room at the temperatures recommended by the manufacturer
|
12/20/2023
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
212
|
Yes
|
No
|
hoist ropes are rouged
|
12/12/2023
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
the state operating certificate in the machine room expired in 2012, update annually with new copy when received from the state
|
12/20/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
Yes
|
Yes
|
replace bad bearing in the machine, elevator red tagged, could not safely complete the 5 year test
|
12/12/2023
|