Inspection
Inspection Details
Equipment ID
13543
13543
Inspection Date
4/26/2023
4/26/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
Instantaneous
Instantaneous
Governor Rope Pull
80/900
80/900
Door Closing Force
NA
NA
External ID
4bb26fc4-80b4-4305-8df0-b75bbe44bf9e
4bb26fc4-80b4-4305-8df0-b75bbe44bf9e
Location
Mallinckrodt Bldg
3600 N 2nd St, St. Louis, MO
Phone: (314) 654-1600
3600 N 2nd St, St. Louis, MO
Phone: (314) 654-1600
Owner
Attn: Mallinckrodt
Mallinckrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Mallinckrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Billing
Attn: Mallinckrodt
Mallinckrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Mallinckrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | ladder up to machine room need to be bolted down at the bottom | 9/14/2021 |
| conversion | conversion | n/a | No | No | Need to replace/service fire extinguisher in machine room tagged 1976 | 9/14/2021 |
| conversion | conversion | n/a | No | No | Post Mo State certificate in machine room | 9/14/2021 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Install missing signage in car A loading class B No passengers | 9/14/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Take corrective action to obtain mac safety rope pull out | 5/6/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Repair ventilation unit connected to controller in machine room | 9/14/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 9/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Install signage in car, load class & no passengers | 9/14/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | Obtain proper pull out safety ropes | 9/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair air conditioner to controller | 9/14/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Provide monthly fire service test & document on log in machine room | 9/14/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Repair rope gripper--emergency brake failed | 5/14/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post current state certificate in machine room | 9/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need testing procedures included in MCP on or before 1/1/22 | 9/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 11/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Repair hoistway door lock at 1R to operate as designed. | 4/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 11/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Governor safety rope pullout shall not exceed 42" (200 fpm or less). Currently pulls 64". Elevator Red Tagged. | 5/1/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | 2.17.12.4 - Rope used as a connection from the safety to the governor rope, including rope wound on the safety-rope drum, shall be made of corrosion resistant/non-magnetic metal (bronze, etc). | 5/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Repair/replace hoistway door unlocking device/pull chain box (2nd landing). | 11/14/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safties failed to operate with governor tripped. | 12/2/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the machine room in a noncombustible frame. | 12/2/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | EMERGENCY LIGHTING shall work with loss of power. Turns on, then off after approx 5sec. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Need to test Runby, Unintended Motion(UP dir), softset Safeties, measure pull out rope length. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Rear Hoistway door at 1st Floor is missing a guide shoe. Shoe is on pit floor. Repair/replace as needed. |