Inspection
Inspection Details
Equipment ID
13544
13544
Inspection Date
4/27/2023
4/27/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
Instantaneous
Instantaneous
Governor Rope Pull
180/840
180/840
Door Closing Force
NA
NA
External ID
1e1a163a-542b-41d5-afc1-d9e4377a4f3d
1e1a163a-542b-41d5-afc1-d9e4377a4f3d
Location
Mallinckrodt Bldg
3600 N 2nd St, St. Louis, MO
Phone: (314) 654-1600
3600 N 2nd St, St. Louis, MO
Phone: (314) 654-1600
Owner
Attn: Mallinckrodt
Mallinckrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Mallinckrodt
PO Box 982201, El Paso, TX 79998
Phone: (314) 654-1760
Email: robert.mohr@mnk.com
Billing
Attn: Mallinckrodt
Mallinckrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Mallinckrodt
3600 N 2nd St, St. Louis, MO 63147
Phone: (314) 654-1760
Email: Ryan.Martin@mnk.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Post current Mo state operating certificate in machine room | 12/10/2018 | ||
conversion | conversion | n/a | Alarm bell not working | 12/10/2018 | ||
conversion | conversion | n/a | Repair emergency phone | 12/10/2018 | ||
conversion | conversion | n/a | Repair pit lighting/ lighting shall be permanent fixture | 12/10/2018 | ||
conversion | conversion | n/a | Repair emergency lighting | 12/10/2018 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/1/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone shall work with and without main power and give proper location. Walkie-talkie is not an approved elevator phone. | 6/4/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Emergency lighting shall work and be of sufficient brightness. | 6/4/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Non-elevator related items shall not be stored in machine room. Remove Freon bottles, roofing adhesives, etc. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | Test Incomplete. Standby Power operation to be tested and verified with 100% capacity. | 6/4/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Put light shall work, a permanent lighting fixture shall be provided in all pits. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Emergency lighting shall work and be of sufficient brightness. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Standby power operation to be tested. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Front gate mechanical bump edge is not working. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | The pit light shall work. A permanent lighting fixture shall be provided in all pits. The light is not working. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Electrical box in machine room above light disconnect needs to have cover installed. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.7 - Sequence operation | 2.13.3.4 | 2.13.3.4.1 - Freight door audible signal for "auto-close" is not working. Visual signal is working. |