Inspection
Inspection Details
Equipment ID
25942
25942
Inspection Date
5/3/2023
5/3/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Sean Commerford
Sean Commerford
Relief Valve Pressure
NA
NA
Slide
3"
3"
Governor Rope Pull
30/100
30/100
Door Closing Force
23F/25R
23F/25R
External ID
fce4bfa4-4291-4515-9571-99e14bbf5015
fce4bfa4-4291-4515-9571-99e14bbf5015
Location
21c Museum Hotel
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
Owner
Attn: Locust Street Property 1 STL, LLC
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Acceptance testing is incomplete. The following items still need to be tested and recorded: Slide, pull out/pull thru, governor electrical & mechanical speeds, door closing pressure, ring & string, fire alarm initiating device testing, emergency power. | 5/3/2023 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | ARU/Battery pack switch missing in disconnect. | 5/3/2023 | |
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Install all missing covers in machine room. | 5/3/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Main and lighting disconnect shall be labeled. | 5/3/2023 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | The following fire service devices failed to recall elevator. Machine room smoke, top of hoistway smoke, and all heat detectors (not tested). | 5/3/2023 |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | 2.3.3 - Top of machine space (hoistway) lighting and outlet shall work. | 5/3/2023 | |
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | x | Pit light switch is not accessible from landing due to obstructions and location. | 5/3/2023 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Top of hoistway smoke needs to be reprogrammed. | 5/4/2023 |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | All heat detectors shall be tested. | 5/4/2023 |
A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | |||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | Front door open button is not functioning on Phase 2 fire service. | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing not complete: The following items still need to be tested/inspected: car door switch and restrictor, governor, safeties, unintended movement, emergency power and door closing force. |