Inspection
Inspection Details
Equipment ID
20639
20639
Inspection Date
5/1/2023
5/1/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
560
560
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
12b9e938-3c80-4d91-93c8-6b14add87cd2
12b9e938-3c80-4d91-93c8-6b14add87cd2
Location
Mercy Rehabilitation Hospital
14561 N Outer 40 Rd, Chesterfield, MO
Phone: (314) 881-4020
14561 N Outer 40 Rd, Chesterfield, MO
Phone: (314) 881-4020
Owner
Attn: Mercy Rehabilitation Hospital
Mercy Rehabilitation Hospital
14561 N Outer 40 Rd, Chesterfield, MO 63017
Phone: (000) 000-0000
Email: dmmullen@mrhsl.com
Mercy Rehabilitation Hospital
14561 N Outer 40 Rd, Chesterfield, MO 63017
Phone: (000) 000-0000
Email: dmmullen@mrhsl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/9/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 10/25/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | The category 5 test shall be conducted and witnessed on the overspeed valve in 2022. | 5/1/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 1/9/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | A category 5 test shall be performed on the overspeed valve within 90 days. Not currently sealed or tagged. Multi-year violation. | 10/25/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 1/9/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/9/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean. Remove excess debris from pit. | 1/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | OSV shall have current test tag. Tested in 2023, but not tagged. | 4/17/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Replace unreadable in-car capacity plate. | 4/17/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. No documentation of any kind for 6/2024 to present. | 4/17/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 4/17/2026 |