Inspection
Inspection Details
Equipment ID
22237
22237
Inspection Date
3/5/2018
3/5/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
Relief Valve Pressure
Slide
28"
28"
Governor Rope Pull
120/470
120/470
Door Closing Force
21
21
External ID
Location
Gallery 1014 @ The Alvern
1014 Locust St, St Louis, MO
Phone: (314) 540-5988
1014 Locust St, St Louis, MO
Phone: (314) 540-5988
Owner
Brandonview
106 W Church, Mascoutah, IL 62258
106 W Church, Mascoutah, IL 62258
Billing
Attn: Brandonview
106 W Church, , IL 62258
106 W Church, , IL 62258
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Car emergency telephone shall work. | 6/15/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Provide "In case of fire" signage at all hall station push buttons. | 1/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | Provide hoist rope data tags. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.11.2.1.3(z) | No | No | Provide governor rope data tags. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 8.11.2.1.1(g) | No | No | Adjust the car door clutch for better operation. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Label disconnects with source location and identification. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(p) | No | No | Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.1 | No | Yes | Rope gripper shall stop the car within 48". The rope gripper operation shall be code compliant - Elevator Red Tagged | 10/22/2020 |
| A17.1-2016 : Elevators | 2.28 - Terminal stopping devices | 8.11.2.1.2(dd) | Yes | No | The governor encoder cable is not connected. If device is not needed, properly remove wiring and device. | 10/22/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. | 10/22/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Unit shall have on-site maintenance documents. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(p) | No | No | Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 8.6.1.7 | No | No | The governor encoder cable is not connected. If device is not needed, properly remove wiring and device. | 7/28/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. | 2/12/2021 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Unit shall have on-site maintenance documents. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. | 3/18/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. | 5/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP shall be provided. Currently missing rescue plan. | 7/28/2025 |