Inspection
Inspection Details
Equipment ID
1879
1879
Inspection Date
5/10/2023
5/10/2023
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Joseph Ottoline
Joseph Ottoline
Relief Valve Pressure
330
330
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
db3ac442-9f1a-4a22-b44e-4b9293889386
db3ac442-9f1a-4a22-b44e-4b9293889386
Location
Ameren Missouri
1901 Chouteau Ave, St. Louis, MO
Phone: (314) 363-4794
1901 Chouteau Ave, St. Louis, MO
Phone: (314) 363-4794
Owner
Attn: Ameren
Ameren U E
1901 Chouteau Ave, St. Louis, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Ameren U E
1901 Chouteau Ave, St. Louis, MO 63103
Phone: (314) 554-3368
Email: facilitiesMgmt&const@ameren.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Unit has oil recovery pump in pit which is for temporary use only. Replace with proper container to allow measurement of oil leakage. | 5/13/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV is not sealed. Perform test on or before next annual inspection date. | 5/13/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.4 Plunger Gripper Testing | Plunger gripper is not sealed. Perform test on or before next annual inspection date. | 5/13/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Provide testing of emergency power. | 5/10/2023 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Provide testing of emergency power selector switch. | 5/10/2023 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Sump unit not plugged in. Determine if working, if not-replace. | 5/13/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Phase II switch improperly mounted in COP, unable to test. Repair as needed. | 5/10/2023 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 5/13/2025 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Provide testing of the elevator on emergency power. | 12/7/2024 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Sump hole has oil in it, remove. | 5/13/2025 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Determine if the sump pump works properly, if not then replace. | 5/13/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 5/13/2025 | ||
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | x | Provide testing of the elevator emergency power selector switch. | 12/4/2025 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Provide testing of the elevator on emergency power. | 12/4/2025 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone works,but goes to the previous contractor., reprogram. | 12/4/2025 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone works,but goes to the previous contractor., reprogram. | 2/12/2026 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Emergency power shall be tested. | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | x | The visual/text communication for assisting passengers unable to communicate verbally or hear shall be operable. |