Inspection
Inspection Details
Equipment ID
16011
16011
Inspection Date
5/12/2023
5/12/2023
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Ryan Williams
Ryan Williams
Relief Valve Pressure
na
na
Slide
11
11
Governor Rope Pull
30/140
30/140
Door Closing Force
26
26
External ID
7c3a91fb-bf26-4b10-bf97-726dd7a4acef
7c3a91fb-bf26-4b10-bf97-726dd7a4acef
Location
Winter Garden Apartments
5708 Kingsbury Pl, St. Louis, MO
Phone: (314) 361-7225
5708 Kingsbury Pl, St. Louis, MO
Phone: (314) 361-7225
Owner
Attn: Winter Garden Preservation, LP
RMC-Related Management Company
60 Columbus Circle, New York, NY 10023
Phone: (212) 801-1073
RMC-Related Management Company
60 Columbus Circle, New York, NY 10023
Phone: (212) 801-1073
Billing
Attn: Winter Garden Apartments
Winter Garden Apartments
5708 Kingsbury Pl, St. Louis, MO 63112
Phone: (314) 361-7225
Email: WinterGardenApts@related.com
Winter Garden Apartments
5708 Kingsbury Pl, St. Louis, MO 63112
Phone: (314) 361-7225
Email: WinterGardenApts@related.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace cracked floor tile in car, tripping hazard | 9/25/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair Fire Service--when simulating smoke dector--car did not respond | 9/24/2018 |
| conversion | conversion | n/a | No | No | Post current State cetificate in machine room | 9/25/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair car floor tile--tripping hazard | 11/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide maintenance control program and place on controller in machine room | 11/11/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and document on log in machine room | 11/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair seismic operation within 30 days--reinspection required | 11/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures located in the MCP on or by January 1, 2022 | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Isolation pads needs replacing | 8/16/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Floor tiles broken and loose needs to be repaired | 8/16/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 8/16/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Replace broken car floor tile | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 5/12/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 8/16/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 8/16/2023 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Repair machine room air conditioner | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing isolation pad on rope shackle in machine room | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide a maintenance control plan. | 8/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair seismic operation 8.4.10.1.1 | 8/16/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | When simulating 1st floor smoke detector car failed to respond | 5/12/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/22/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 11/22/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post current state certificate in the machine room | 12/8/2025 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | Yes | No | Replace Ropes - Red Rouge & reduced diameter- Within 30 Days | 12/8/2025 |
| A17.1-1996 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 1206.7 | Yes | Yes | Perform Monthly Fire service test and document on the log posted in the Machineroom | 12/8/2025 |