Inspection
Inspection Details
Equipment ID
6918
6918
Inspection Date
5/10/2023
5/10/2023
Inspection Type
Alteration
Alteration
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
William Bracht
William Bracht
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
b090c913-9c47-4e45-9e08-ab923109dc29
b090c913-9c47-4e45-9e08-ab923109dc29
Location
St. Louis Marriott West
660 Maryville Centre Dr, St. Louis, MO
Phone: (314) 878-3005
660 Maryville Centre Dr, St. Louis, MO
Phone: (314) 878-3005
Owner
Attn: St. Louis Marriott West
PMO III, LLC
660 Maryville Centre Dr, St. Louis, MO 63141
Phone: (000) 000-0000
Email: jkoleske@lhmc.com
PMO III, LLC
660 Maryville Centre Dr, St. Louis, MO 63141
Phone: (000) 000-0000
Email: jkoleske@lhmc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Repair car door restrictor | 5/24/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Governor rope pull through jaws and not setting safeties. | 6/3/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Repair door knob on machine room. | 10/19/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated operating certificate in machine room. | 10/19/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 2/26/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are showing signs of stretching, need to replace ropes within 60 days. Re-inspection required | 2/26/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/11/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 3/11/2024 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | The counterweight is touching the oil buffer when the elevator travels to the top floor. The hoist ropes shall be shortened to provide a minimum runby of 6". Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Cartop inspection station shall work, repair as needed. | 2/12/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform the following tests to complete 5 year inspection: full load, full speed safeties, full load car buffer, counterweight buffer, 125% brake, overspeed governor jaw and switch speeds, overspeed governor pull thru, & safeties pull out. Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 2/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Cartop inspection station shall work, repair as needed. | 2/12/2026 |