Inspection
Inspection Details
Equipment ID
1316
1316
Inspection Date
5/12/2023
5/12/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Bryan Wright
Bryan Wright
Relief Valve Pressure
460
460
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
22F 24R
22F 24R
External ID
3470f41d-16ca-4b84-bd1c-d87af2e6ca46
3470f41d-16ca-4b84-bd1c-d87af2e6ca46
Location
Loch Lloyd Country Club
16750 S Country Club Dr, Village of Loch Lloyd, MO
Phone: (816) 322-1022
16750 S Country Club Dr, Village of Loch Lloyd, MO
Phone: (816) 322-1022
Owner
Attn: Chris Brems
Loch Lloyd Country Club
16750 S Country Club Dr, Village of Loch Lloyd, MO 64012
Phone: (816) 509-1489
Email: chrisb@lochlloyd.com
Loch Lloyd Country Club
16750 S Country Club Dr, Village of Loch Lloyd, MO 64012
Phone: (816) 509-1489
Email: chrisb@lochlloyd.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Pit was wet and filthy [2yr notice] | 7/30/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Fire int. device not working top floor that was added | 5/24/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Supply required monthly FFS test log | 7/30/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt of operation displayed | 4/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emg phone not working | 5/20/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit has standing water an oil in it | 4/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Mach.room door needs to be self closing an self locking | 4/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door not self closing or self locking | 4/16/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | CURRENT CIRT NOT DISPLAYED | 4/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | water an oil in pit needs to be cleaned up | 4/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Oil in pit. | 4/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light not working. | 4/16/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | No | No | Rail guide shoes worn, causing car movement. | 4/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm not working on battery power, emergency phone ok. | 5/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Tile at main floor landing level presents a trip hazard, repair tile flush with elevator landing sill. | 4/16/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room when received. | 4/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | machine this is room door not self closing or self locking. This is a repeat violation reinsp. required | 4/16/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emg phone not working no line voltage 14 days to fix or repair | 10/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current insp cirt posted | 4/16/2025 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | door restrictor on front door has been removed replace or repair | 10/1/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit floor covered in oil debris in pit reinsp required | 4/16/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | No | No | lower guide shoes missing inserts causing excessive movement of car reinsp required | 4/16/2025 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | leak dn test was 3/4 inch. in 15 mins gate valve closed an no noticeable difference in oil tank futher testing needed reinsp required 8.6.5.14.2(b) | 4/16/2025 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | replace packing on cyl head an provide 5 gal oil collection can reinsp required | 4/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit lt not working reinsp required | 4/16/2025 |