Inspection
Inspection Details
Equipment ID
12527
12527
Inspection Date
5/5/2023
5/5/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
ca3b2659-1cbb-4f79-b1e5-dc3d4c785685
ca3b2659-1cbb-4f79-b1e5-dc3d4c785685
Location
Forest Park Community College
5600 Oakland Ave, St. Louis, MO
Phone: (314) 644-9151
5600 Oakland Ave, St. Louis, MO
Phone: (314) 644-9151
Owner
Attn: John Duarte
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 435-9505
Email: jduarte@stlcc.edu
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 435-9505
Email: jduarte@stlcc.edu
Billing
Attn: Accts payable
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 539-5263
Email: apayable@stlcc.edu
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 539-5263
Email: apayable@stlcc.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace the missing pick up rollers at the 2nd and 3rd floor. | 1/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The emergency light shall work. | 1/30/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the machine room. | 1/30/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The in car stop switch shall be bypassed on Phase 1 fire recall. | 2/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current MO State operating certificate in the machine room. | 3/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired. | 6/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No certificate in machine room. | 6/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Emergency lowering unit is not working. | 5/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | There is no fire extinguisher. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. | 5/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/5/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The presense of an overspeed valve has been confirmed, along with an installation date of 1999. The overspeed valve shall be scheduled for the category 5 test. | 2/9/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/9/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be operational. | 2/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC type fire extinguisher shall be provided in the machine room. | 2/9/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/9/2026 |