Inspection
Inspection Details
Equipment ID
22238
22238
Inspection Date
5/16/2023
5/16/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
8f4c2adb-3387-4a82-9d5b-8f54eedf7cc8
8f4c2adb-3387-4a82-9d5b-8f54eedf7cc8
Location
Gallery 1014
1014 Locust St, St. Louis, MO
Phone: (314) 540-5988
1014 Locust St, St. Louis, MO
Phone: (314) 540-5988
Owner
Attn: Brandonview
Brandonview
106 W Church St, Mascoutah, IL 62258
Phone: (314) 328-7900
Fax: (314) 480-7169
Email: accounting@stlluxury.com
Brandonview
106 W Church St, Mascoutah, IL 62258
Phone: (314) 328-7900
Fax: (314) 480-7169
Email: accounting@stlluxury.com
Billing
Attn: Brandonview
Brandonview
106 W Church St, Mascoutah, IL 62258
Phone: (314) 328-7900
Fax: (314) 480-7169
Email: gallery1014@stlluxury.com
Brandonview
106 W Church St, Mascoutah, IL 62258
Phone: (314) 328-7900
Fax: (314) 480-7169
Email: gallery1014@stlluxury.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Car emergency telephone shall work. | 6/15/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Provide "In case of fire" signage at all hall station push buttons. | 1/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | Provide hoist rope data tags. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 8.11.2.1.3(z) | No | No | Provide governor rope data tags. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 8.11.2.1.1(g) | No | No | Adjust the car door clutch for better operation. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Label disconnects with source location and identification. | 6/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(p) | No | No | Label the disconnects with the name, location and breaker numbers of the panel feeding the disconnect. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | The machine room lighting is dim and does not meet the minimum requirement. Provide code compliant machine room lighting. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The category 5 portion of the test is not complete. Weight portion of the test is still required. | 2/12/2021 |
| A17.1-2016 : Elevators | 2.28 - Terminal stopping devices | 8.11.2.1.2(dd) | Yes | No | The governor encoder cable is not connected. If device is not needed, properly remove wiring and device. | 2/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. | 2/12/2021 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | The elevator pit shall be kept dry. Remove water from the pit and correct source of water leak. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Unit shall have on-site maintenance documents. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The category 5 portion of the test is not complete. Weight portion of the test is still required. | 5/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone answering service could not identify the location of the elevator. The 24 hour monitoring service shall be able to identify the elevator from which the call is originating. | 5/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP shall be provided. Currently missing rescue plan. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 8/23/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency alarm bell shall be operational. | 8/23/2022 |