Inspection
Inspection Details
Equipment ID
12593
12593
Inspection Date
3/17/2023
3/17/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
529a540d-bb92-4579-b54f-1b005f0b2a39
529a540d-bb92-4579-b54f-1b005f0b2a39
Location
West County Center
80 W COUNTY CTR, DES PERES, MO
Phone: (314) 984-0450
80 W COUNTY CTR, DES PERES, MO
Phone: (314) 984-0450
Owner
Attn: Andrew Goldacker
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
CBL Properties/West County Center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post Mo State certificate in machine room | 7/25/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 7/25/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone. | 7/8/2019 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | There is an 1 1/8" gap between the cop and the car door. Needs to be fixed. Reinspect. | 7/25/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Light needs to work in the pit. | 7/8/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 10/30/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 7/25/2019 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | No | No | The gap between elevator cab and car door are over 3/8" when the door is in the closed position. | 9/22/2020 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean elevator car top. | 9/22/2020 |
| A17.1-1996 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 1001.2(c)(19) | No | No | Toe guard is hitting the landing sill guard in elevator pit. | 9/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Car directional arrows, missing lens-provide. | 3/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not provide 2 way communication, needs repaired. Re-inspection required | 3/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Provide missing directional arrow lens | 3/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit is not working properly at the time of inspection. |