Inspection
Inspection Details
Equipment ID
25330
25330
Inspection Date
5/11/2023
5/11/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Thomas Suedkamp
Thomas Suedkamp
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
cc9ad458-c872-4dda-af4d-61982edd6573
cc9ad458-c872-4dda-af4d-61982edd6573
Location
Lofts at the Hupp
1815 Locust St, St. Louis, MO
Phone: (314) 338-1076
1815 Locust St, St. Louis, MO
Phone: (314) 338-1076
Owner
Attn: Bethany Kelly
1815 Locust LLC
1815 Locust, St. Louis, MO 63103
Phone: (231) 750-1005
Email: bkelly@keeleyproperties.com
1815 Locust LLC
1815 Locust, St. Louis, MO 63103
Phone: (231) 750-1005
Email: bkelly@keeleyproperties.com
Billing
Attn: Bethany Kelly
1815 Locust LLC
1815 Locust, St. Louis, MO 63103
Phone: (231) 750-1005
Email: ap@keeleyproperties.com
1815 Locust LLC
1815 Locust, St. Louis, MO 63103
Phone: (231) 750-1005
Email: ap@keeleyproperties.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | Phase 1 & 2 fire service and all initiating devices shall be tested. | 6/30/2021 |
| A17.1-2016 : Elevators | 4.8 - Hoistway enclosure | 8.10.2.2.4(h) | Yes | No | Screws protruding into the hoistway shall be removed. | 6/30/2021 |
| A17.1-2016 : Elevators | 4.8 - Hoistway enclosure | 8.10.2.2.4(h) | Yes | No | The door at the top of the hoistway shall be blocked up. | 6/30/2021 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | Beams in the back of the hoistway and concrete ledge in the pit shall be beveled to an angle not less than 75 degrees. | 6/30/2021 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | Yes | No | The machine room door shall be self-closing and self-locking. | 6/30/2021 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 4/19/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | No | No | Phone line monitor is not working correctly | 6/7/2022 |
| A17.1-2016 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4 | No | No | Counterweight derailment device is not working | 4/5/2022 |
| A17.1-2016 : Elevators | 11.10 - Governor, Overspeed Switch | 2.18.7.2 | No | No | Govenor tail sheave switch is not working | 4/5/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working correctly, repair as needed. | 6/8/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | No | No | Phone line monitoring not working correctly, repair as needed. Reinspect required. | 4/5/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Video monitoring is not working and shall be operational. (Phone is working) | 2/29/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 12/30/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Video monitoring does not work. | 12/30/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | A two-way communication means between the car and a location staffed by authorized personnel shall be provided. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | Each elevator shall be provided with auxiliary lighting and shall conform to the following: (3) systems shall be designed so that an audible or visual signal notifies authorized personnel when on lamp or set of lamps is not functional. |