Inspection
Inspection Details
Equipment ID
10511
10511
Inspection Date
5/22/2023
5/22/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
n
n
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
364f46f3-3c6e-448e-acb3-2b5e5b73cbac
364f46f3-3c6e-448e-acb3-2b5e5b73cbac
Location
Bank of America- St. Louis
4625 Lindell Blvd, St. Louis, MO
Phone: (314) 655-6000
4625 Lindell Blvd, St. Louis, MO
Phone: (314) 655-6000
Owner
Attn: TCG BOA MO Holdings, LLC
TCG BOA MO Holdings, LLC
425 5th Ave, 30th Fl, New York, NY 10018
Phone: (314) 655-6000
TCG BOA MO Holdings, LLC
425 5th Ave, 30th Fl, New York, NY 10018
Phone: (314) 655-6000
Billing
Attn: Deloitte Management Office
Cushman and Wakefield
100 S 4th St, St. Louis, MO 63102
Phone: (314) 241-0150
Email: Ryan.Ching@cushwake.com
Cushman and Wakefield
100 S 4th St, St. Louis, MO 63102
Phone: (314) 241-0150
Email: Ryan.Ching@cushwake.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase II not working | 2/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Drive machine brake pins not freely moving, perform maintenance. | 10/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide callback log and maintenance control program. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | No | No | Provide braille/tactile plates on all jambs, as needed. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 8.11.2.1.3(k) | No | No | Provide corrected crosshead data plate. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.2 | Yes | No | Seal governor. Was never done from final acceptance. | 10/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone rings to previous contractor. Reprogram. | 10/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Drive machine brake pins not freely moving, perform maintenance as needed. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide missing maintenance: Call Back Log | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide maintenance control program. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current elevator operating certificate in machine room. | 11/4/2020 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | Provide braille/tactile plates on all jambs, as needed. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | No | No | Provide correct crosshead data plate. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.7.1.8 | No | No | Provide corrected data plate on governor in machine room. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.2 | Yes | No | Seal governor. Was not done on final acceptance. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean and dry. | 4/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be answered by proper personnel 24x7. | 4/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 4/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the elevator machine room | 11/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Current fire extinguisher located in the elevator machine room is expired. |