Inspection
Inspection Details
Equipment ID
19079
19079
Inspection Date
6/6/2023
6/6/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Sam Cones
Sam Cones
Relief Valve Pressure
570
570
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
284eb407-394c-412d-b1c5-c9fc7d141911
284eb407-394c-412d-b1c5-c9fc7d141911
Location
Baymont Inn- Branson by Wyndham
2719 W 76 Country Blvd, Branson, MO
Phone: (417) 334-7000
2719 W 76 Country Blvd, Branson, MO
Phone: (417) 334-7000
Owner
Attn: Stanley Merriman
Harry Patel
2719 W 76 Country Blvd, Branson, MO 65616
Phone: (417) 334-7000
Harry Patel
2719 W 76 Country Blvd, Branson, MO 65616
Phone: (417) 334-7000
Billing
Attn: Stanley Merriman
Baymont Inn- Branson by Wyndham
2719 W 76 Country Blvd, Branson, MO 65616
Phone: (417) 559-6936
Alt Phone: (417) 334-7000
Email: baymontbransongm@gmail.com
Baymont Inn- Branson by Wyndham
2719 W 76 Country Blvd, Branson, MO 65616
Phone: (417) 559-6936
Alt Phone: (417) 334-7000
Email: baymontbransongm@gmail.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean up the oil and debris from the pit floor. | 8/20/2019 |
| conversion | conversion | n/a | No | No | Replace the burnt up exhaust fan in the car ceiling. | 8/20/2019 |
| conversion | conversion | n/a | No | No | Obtain and display a current state operating certificate in the machine room | 8/20/2019 |
| conversion | conversion | n/a | No | No | Replace the two 20 amp breakers tied together with a piece of copper wire with an approved device or replace the breaker with an two pole breaker. | 8/20/2019 |
| conversion | conversion | n/a | No | No | Replace the broken arrow board in the jamb. | 8/20/2019 |
| conversion | conversion | n/a | No | No | Repair the machine room door as it is to be self closing, self latching. | 8/20/2019 |
| conversion | conversion | n/a | No | No | Replace the missing receptical cover in the pit. | 8/20/2019 |
| conversion | conversion | n/a | No | No | Supply a non combustible holder with clear cover for the state operating certificate in the machine room | 8/20/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean up the gunk from the pit floor. | 8/20/2019 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Replace the missing fire extinguisher in the machine room. | 11/15/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Have the expired fire extinguisher re-certified. | 11/6/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove the stored materials and equipment from the elevator equipment room. | 11/6/2024 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | Yes | No | Re-pack the leaking jack seal. | 11/6/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean up the oil from the pit floor. | 11/6/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Replace the machine room door that has been damaged heavely and replace the door lock as it is to be self closing and self locking alwas locked outside and never locked inside. | 8/8/2025 |