Inspection
Inspection Details
Equipment ID
1652
1652
Inspection Date
1/12/2018
1/12/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Glen Kuehner
Glen Kuehner
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
34709b02-ae6b-4d7d-9fe2-b18948158956
34709b02-ae6b-4d7d-9fe2-b18948158956
Location
10 South Broadway Bldg
10 S BROADWAY, SAINT LOUIS, MO
10 S BROADWAY, SAINT LOUIS, MO
Owner
Hertz Investment Group
10 S BROADWAY STE 100, SAINT LOUIS, MO 63102-1728
10 S BROADWAY STE 100, SAINT LOUIS, MO 63102-1728
Billing
Attn: Hertz Investment Group
10 S BROADWAY STE 100, SAINT LOUIS, MO 63102-1728
10 S BROADWAY STE 100, SAINT LOUIS, MO 63102-1728
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency light not working. | 1/14/2019 |
| A17.1-1996 : Elevators | 2.20 - Winding drum machine and slack cable device | 208.1 | Yes | No | Ring and string not working. | 4/24/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 206.7 | Yes | Yes | Suspension ropes do not meet minimum requirements, need to be replaced. ELEVATOR RED TAGGED. | 10/21/2019 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 111 | No | No | New door gibs need on Floors 16, 17, 19, 21, all rusted through. | 7/15/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 210.1e | No | No | Floor 16 needs new pick up rollers. | 7/15/2020 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | Counterweight bracket is missing rings for earthquake ring and string. | 10/21/2019 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | No | No | Floors 16, 17, 19,21 need new door gibs. The are almost rusted through. | 7/15/2020 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | Counterweight bracket is missing rings for earthquake ring and string. Test needs to be conducted. | 2/21/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fireman's emergency service shall be tested. Re-inspection required | 10/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Shorten Hoist cables counter weights stricking buffer when car is at top landing | 1/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency Phone | 7/14/2025 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 201.4h | Yes | No | Counterweight striking buffer when car is at the top ?oor. Shorten hoist cables to meet code parameters. | 7/14/2025 |