Inspection
Inspection Details
Equipment ID
21380
21380
Inspection Date
6/7/2023
6/7/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
1750
1750
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
27
27
External ID
7f7f1dd4-9d23-458d-9b85-a4dd4acdefdb
7f7f1dd4-9d23-458d-9b85-a4dd4acdefdb
Location
Sumner High School
4268 COTTAGE AVE, SAINT LOUIS, MO
Phone: (314) 633-9103
4268 COTTAGE AVE, SAINT LOUIS, MO
Phone: (314) 633-9103
Owner
Attn: Rosmon Johnson
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Rosmon.Johnson@slps.org
St. Louis Board of Education
801 N 11th St, St. Louis, MO 63101
Phone: (314) 535-2500
Email: Rosmon.Johnson@slps.org
Billing
Attn: Cardinal Elevator
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: lisa@cardinalelevator.com
Cardinal Elevator
2851 Barrett Station Rd, St. Louis, MO 63021
Phone: (314) 939-9222
Email: lisa@cardinalelevator.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The machine room shall be kept clean. Clean the machine room. | 4/8/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | This is a roped hydraulic LU/LA. A category 1 test of the safeties shall be performed and witnessed. | 4/8/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.3 - Top-of-car operating device | 8.11.2.1.3(c) | No | No | The car top inspection station does not operate as designed and would not operate properly. The device shall be repaired or replaced to operate as designed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The machine room lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed. | 6/7/2023 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Perform the required tests on the Overspeed Valve | 6/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.1 Means of Communication (Red Tag) | Yes | Yes | No operating phone or alarm Repair as needed | 6/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 8.11.3.2.5 Pressure Switch (Re-Inspection) | Yes | No | Repair inoperative low pressure switch | 6/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Provide at least 19 foot candles of illumination in the machine room | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Perform the required Cat 5 tests on the Overspeed Valve | 5/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 8.11.3.2.5 Pressure Switch (Re-Inspection) | Yes | No | Repair inoperative low pressure switch | 5/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Increase the machine room lighting to 19ft candles minimum | |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | OSV is due for testing, provide. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Provide machine room lighting (foot candles at the floor ) to be code compliant. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | No | No | Water is entering the hoistway from the top. Repair as needed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. |