Inspection
Inspection Details
Equipment ID
14375
14375
Inspection Date
6/12/2023
6/12/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Dennis Smith
Dennis Smith
Relief Valve Pressure
850
850
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
14
14
External ID
e31a12e8-e849-4294-97d0-656fdfcf9bff
e31a12e8-e849-4294-97d0-656fdfcf9bff
Location
Hy-Vee- St. Joseph
201 N BELT HWY, SAINT JOSEPH, MO
Phone: (816) 232-9750
201 N BELT HWY, SAINT JOSEPH, MO
Phone: (816) 232-9750
Owner
Attn: Hy-Vee- St. Joseph
Hy-Vee- St. Joseph
1501 SE 5th St, Des Moines, IA 50315
Phone: (000) 000-0000
Hy-Vee- St. Joseph
1501 SE 5th St, Des Moines, IA 50315
Phone: (000) 000-0000
Billing
Attn: Hy-Vee- St. Joseph
Hy-Vee- St. Joseph
201 N Belt Hwy, St. Joseph, MO 64506
Phone: (000) 000-0000
Hy-Vee- St. Joseph
201 N Belt Hwy, St. Joseph, MO 64506
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | No | Phone does not work | 6/25/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | Emergency light does not work. | 6/25/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 12/17/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency light does not operate. | 10/22/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine room | |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | Eliminate excessive gap between hoistway door panels in fully closed position. | |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | Eliminate gap between center opening hoistway doors in fully closed position | |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | Eliminate gap between center opening car doors in fully closed position. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove non-elevator related material from the machine room | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | state operating certificate not displayed | |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | KEEP A CLEAR PASSAGEWAY IN FRONT OF ELEVATOR MACHINE ROOM DOOR | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | DISPLAY OPERATING CERTIFCATE IN MACHINE ROOM | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | REMOVE ALL NON-ELEVATOR ITEMS FROM MACHINE ROOM |