Inspection
Inspection Details
Equipment ID
12241
12241
Inspection Date
6/1/2023
6/1/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
460
460
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
19
19
External ID
31ba7b05-6b78-43b5-b999-b406b36c2a49
31ba7b05-6b78-43b5-b999-b406b36c2a49
Location
SSM-St. Louis University Hospital Legacy Building
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Owner
Attn: Janet Dickson
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Phase II Fire service key bezel needs to be replaced | 9/3/2019 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Door restrictor is not working. | 9/3/2019 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Car top light needs to be repaired. | 9/3/2019 | ||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Phase I car panel light not working. | 9/3/2019 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated Missouri Operating Certificate in machine room | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Repair call cancel button. Cannot shut elevator off. Only elevator in building that goes to 2 and 4 floors. Reinspect 30 days | 6/24/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Replace phase II bezel so off hold on car key switch can be read | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Call cancel button on Phase 2 fire service does not work, needs repaired. Re-inspection required | 5/13/2025 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Car door restrictor does not work, needs repaired. Re-inspection required | 5/13/2025 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A written copy of the MCP shall be kept in the machine room for each unit. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Could not access electrical panel to test emergency lights. Restricted access floor, Need to test emergency lights. Re-inspection required | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Need to replace phase II key switch bezel. All wording (off, on & hold) are missing | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Need to replace worn out and damaged car top guide rollers | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | x | Elevator car door reopening device (light ray) does not work. Repair ore replace light ray. Re-inspection required | ||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Call cancel button on phase II fire service does not work, repair needed. Cannot shut elevator down. Only elevator to move patients from floors 2 and 4. Re-inspection required | ||