Inspection
Inspection Details
Equipment ID
13329
13329
Inspection Date
6/16/2023
6/16/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
22
22
External ID
6163d38c-756f-4c54-8217-e26148b8cd2b
6163d38c-756f-4c54-8217-e26148b8cd2b
Location
Lammert Building
911 Washington Ave, St. Louis, MO
Phone: (314) 241-7500
911 Washington Ave, St. Louis, MO
Phone: (314) 241-7500
Owner
Attn: Technology Entrepreneur Center T-Rex
Technology Entrepreneur Center T-Rex
911 Washington Ave, St. Louis, MO 63101
Phone: (314) 241-7500
Email: gwyn@downtowntrex.org
Technology Entrepreneur Center T-Rex
911 Washington Ave, St. Louis, MO 63101
Phone: (314) 241-7500
Email: gwyn@downtowntrex.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (E) - Machines | (E)1 | No | No | Traction machine is making a loud noise and vibrating. Repair | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Turn down fire tabs on all hoistway doors. | 3/25/2026 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Test brake with 125% rated load. Did not red tag. | 10/21/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Test car and counterweight buggers at rated speed. Did not red tag. | 10/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site | 3/25/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Ropes failed gauge test needs replacing | 3/25/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 3/25/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist ropes, red rouge reduced diameter within 30 days | 5/13/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Make pit light operable | 3/25/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Make pit stop switch operable. | 3/25/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit | 3/25/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Adjust car door operator. Excessive force | 3/25/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Complete 5 year test. | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Pit stop switch is functional but toggle switch is broken off. Toggle needs replaced. |