Inspection
Inspection Details
Equipment ID
11714
11714
Inspection Date
6/15/2023
6/15/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
340
340
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
0e0a90e1-b913-41db-807e-efe8198ad686
0e0a90e1-b913-41db-807e-efe8198ad686
Location
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
1201 N Woodbine Rd, St. Joseph, MO
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Owner
Attn: Kerra Flatt
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO 64506
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Stoney Creek Inn
1201 N Woodbine Rd, St. Joseph, MO 64506
Phone: (816) 901-9600
Email: kerra.flatt@stoneycreekhotels.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.37 - Pressure Switch | 306.14 | Yes | No | Need to provide pressure switch on control valve. | 4/11/2019 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 6/25/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter operating instructions next to hall fire keyswitch | 11/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Momentarily pushing car door open button causes doors to fully open while elevator is on firefighter operation phase 2. 14 days to repair before red tag. | 6/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 1/5/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions next to hall fire service keyswitch | 11/8/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 11/8/2021 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Car door restrictor does not function | 1/5/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. Phone needs to be reprogrammed | 6/15/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE DOES NOT RING OUT | 8/16/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | non elev materials being stored in machroom | 9/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit floor covered in oil | 9/23/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | smoke head in mach room not working | 8/21/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Smoke head in mach room not working | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Phase II not working |